Scroll Mini Heat Pump
Model | AC+H(R)F08÷50T |
Brand | AC+ |
Unit | set |
Min order | 1 |
Supply ability | 1000 sets per month |
Payment | 50% T/T as deposit before delivery |
Port | Tianjin |
Certification | ISO 9001/14001/18001 |
Place | China |
Packaging | Export Standard Package |
FEATURES scroll mini heat pump
STRUCTURE
Air source heat pump /Mini scroll heat pump with Panels and base frame are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
HERMETIC COMPRESSORS
Mini Heat pump Single phase (mod.08÷12.5) compressors, 3-phase scroll compressor (mod.16÷50), with thermal overload cut-out and crankcase heater mounted on rubber vibration isolators.
Models 08÷12.5 are available also with 3-phase scroll compressor.
AXIAL FANS
Air to water heat pump External rotor type axial fans, equipped with single phase direct drive motors, low noise 6 poles, protection level IP54, provided with a protective outlet grille.
EVAPORATOR
R22 heat pump High efficiency tube in tube heat exchanger, factory insulated with flexible close cell material.
CONDENSER
Coils are consisting of seamless copper tubes mechanically expanded into blue hydrophilic aluminum fins, protected with flexible plastic grill.
REFRIGERANT CIRCUIT
Air source water heat pump with Copper tube connection with charge valve, filter drier (smaller size), gas-liquid separator, thermostatic expansion valve (expansion capillary tubes for smaller size), low pressure switch with automatic reset, high pressure switch with manual reset.
The heat pump unit is completed also with 4-way valve, liquid receiver and one way valve.
HYDRONIC CIRCUIT
Vertical heat pump with Built with air vent valve, water drain connection, water circuit safety valve, water pump (For smaller size than 30 model), expansion vessel, male-threaded hydraulic connectors and without water storage tank..
ELECTRIC PANEL
consists of:
l Compressor contactor;
l Water pump contactor;
l Compressor protection breaker;
l Water pump protection breaker
l Fan motor protection breaker;
l Control circuit protection breaker;
l Phase sequence relay (only for 3-phase power supplied units);
l Fan speed regulator (Optional);
l Programmable microprocessor controller;
l Heat recovery functions (Optional)
NOMENCLATURE
AC+H R C F 08 T L | ||
Mini heat pump Unit type: R : heat pump -- : cooling only | Refrigerant type --: R22 A: R410a B: R290 C: R407c |
TECHNICAL DATA
* Ambient temperature 35ºC; evaporator water in/out 12/7 ºC;
** Ambient temperature DB 7 ºC, WB 6 ºC; condenser water in/out temperature 40/45 ºC;
*** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field (fan side).
OVERALL DIMENSIONS
Mod. 08÷20
Model | A | B | C | D | E | F |
HRF8TL | 1500 | 500 | 600 | 1105 | 1140 | 450 |
HRF10TL | 1600 | 500 | 870 | 1350 | 1390 | 450 |
HRF12.5TL | 1600 | 500 | 870 | 1350 | 1390 | 450 |
HRF16TL | 1700 | 500 | 870 | 1450 | 1490 | 450 |
HRF20TL | 1700 | 500 | 870 | 1450 | 1490 | 450 |
Mod. 08÷16
Air source Water Heat pump /Mini scroll heat pump with Axial Fans, Scroll Compressors 2ton-15 ton R22
AC+H(R)F08÷50T
Cooling capacity: 8.1÷49.5 kW